Deep Sea Electronics DSE6110 MKII Auto Start Control Module (CC)
Sale!

Deep Sea Electronics DSE6110 MKII Auto Start Control Module (CC)

Original price was: $422.27.Current price is: $413.83.

**Please Note: The DSE6110-35 has been discontinued and is no longer available. If ordered, the recommended replacement DSE6110-05 will be shipped.

The DSE6110 MKIII is an Auto Start Control Module suitable for a wide variety of single, diesel or gas, genset applications.

Monitoring an extensive number of engine parameters, the module will display warnings, shutdown and engine status information on the back-lit LCD screen, illuminated LEDs and remote PC.

The module includes USB connection and dedicated DSENet® terminals for system expansion.

The module is compatible with electronic (CAN) and non-electronic (magnetic pick-up/alternator sensing) engines and offers an extensive number of flexible inputs, outputs and extensive engine protections so the system can be easily adapted to meet the most demanding industry requirements.

The extensive list of features includes enhanced event and performance monitoring, remote communications & PLC ?functionality. The modules can be easily configured using the DSE Configuration Suite PC software. Selected front panel editing is also available.

OVERALL SIZE
216 mm x 158 mm x 43 mm (8.5” x 6.2” x 1.5”)

PANEL CUTOUT SIZE
184 mm x 137 mm (7.2” x 5.3”)

MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)

WEIGHT
0.5kg

PRODUCT VARIANTS
6110-05 – 6110 MKIII Auto Start Control Module

DC SUPPLY

CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
5 V for up to 1 minute

CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained
during cranking.

MAXIMUM OPERATING CURRENT
260 mA at 12 V, 150 mA at 24 V

MAXIMUM STANDBY CURRENT
145 mA at 12 V, 85 mA at 24 V

CHARGE FAIL/EXCITATION RANGE
0 V to 35 V

GENERATOR & MAINS (UTILITY)

VOLTAGE  RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz

MAGNETIC PICKUP

VOLTAGE  RANGE
+/- 0.5 V to 70 V

FREQUENCY RANGE
10,000 Hz (max)

INPUTS

DIGITAL INPUTS A to H
Negative switching

ANALOGUE INPUTS A & D
Configurable as:
Negative switching digital input
0 V to 10 V sensor
4 mA to 20 mA sensor
Resistive sensor

ANALOGUE INPUTS B & C
Configurable as:
Negative switching digital input
Resistive sensor

OUTPUTS

OUTPUT A & B (FUEL & START)
10 A DC at supply voltage

AUXILIARY OUTPUTS C, D, E,  F, G & H
2 A DC at supply voltage

 

Description

**Please Note: The DSE6110-35 has been discontinued and is no longer available. If ordered, the recommended replacement DSE6110-05 will be shipped. The DSE6110 MKIII is an Auto Start Control Module suitable for a wide variety of single, diesel or gas, genset applications. Monitoring an extensive number of engine parameters, the module will display warnings, shutdown and engine status information on the back-lit LCD screen, illuminated LEDs and remote PC. The module includes USB connection and dedicated DSENet® terminals for system expansion. The module is compatible with electronic (CAN) and non-electronic (magnetic pick-up/alternator sensing) engines and offers an extensive number of flexible inputs, outputs and extensive engine protections so the system can be easily adapted to meet the most demanding industry requirements. The extensive list of features includes enhanced event and performance monitoring, remote communications & PLC ?functionality. The modules can be easily configured using the DSE Configuration Suite PC software. Selected front panel editing is also available. OVERALL SIZE 216 mm x 158 mm x 43 mm (8.5” x 6.2” x 1.5”) PANEL CUTOUT SIZE 184 mm x 137 mm (7.2” x 5.3”) MAXIMUM PANEL THICKNESS 8.0 mm (0.3”) WEIGHT 0.5kg PRODUCT VARIANTS 6110-05 – 6110 MKIII Auto Start Control Module

DC SUPPLY

CONTINUOUS VOLTAGE RATING 8 V to 35 V Continuous 5 V for up to 1 minute CRANKING DROPOUTS Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking. MAXIMUM OPERATING CURRENT 260 mA at 12 V, 150 mA at 24 V MAXIMUM STANDBY CURRENT 145 mA at 12 V, 85 mA at 24 V CHARGE FAIL/EXCITATION RANGE 0 V to 35 V

GENERATOR & MAINS (UTILITY)

VOLTAGE  RANGE 15 V to 415 V AC (Ph to N) 26 V to 719 V AC (Ph to Ph) FREQUENCY RANGE 3.5 Hz to 75 Hz

MAGNETIC PICKUP

VOLTAGE  RANGE +/- 0.5 V to 70 V FREQUENCY RANGE 10,000 Hz (max)

INPUTS

DIGITAL INPUTS A to H Negative switching ANALOGUE INPUTS A & D Configurable as: Negative switching digital input 0 V to 10 V sensor 4 mA to 20 mA sensor Resistive sensor ANALOGUE INPUTS B & C Configurable as: Negative switching digital input Resistive sensor

OUTPUTS

OUTPUT A & B (FUEL & START) 10 A DC at supply voltage AUXILIARY OUTPUTS C, D, E,  F, G & H 2 A DC at supply voltage  

Additional information

Weight 3 lbs